Sample qualifying storm events, July 1 to December 31
Between July 1 and December 31, 2 times.
Collect and analyze samples from two Qualifying Storm Events (QSEs) between July 1 and December 31, at every discharge location (unless a representative-sampling reduction applies), within 4 hours of the start of discharge or of the start of operations if the QSE began in the previous 12 hours. Analyze TSS, oil and grease, pH, Table 1 parameters for the SIC code, and any facility-specific, impaired-water, TMDL, Regional Board and ELG parameters.
- Does not apply if: inactive mining certification in effect.
- If you are in a compliance group: once.
- If you have certified a sampling frequency reduction: once.
- If you are in a compliance group and you have certified a sampling frequency reduction: once per reporting year.
- Nothing is filed; keep the record at the facility.
- Keep the records 5 years.
Source: Industrial General Permit Order (conformed, as amended 2015 and 2018), section XI.B.2; XI.B.4-6, page 43
"The Discharger shall collect and analyze storm water samples from two (2) QSEs within the first half of each reporting year (July 1 to December 31)"Open the permit at this section